Chiller Tube Maintenance: A Step-by-Step Guide for Long-Term Efficiency

Regular chiller tube maintenance is essential for keeping HVAC systems working at maximum efficiency. While chillers may receive less attention during cooler months, periods of low demand are actually the ideal time to inspect, clean, and optimize chiller tubes before peak operating seasons return.

Chiller tubes play a critical role in heat transfer and overall system performance. When tubes become fouled with scale or mineral deposits, energy efficiency can decline significantly—often leading to higher operating pressures, increased energy consumption, and reduced cooling capacity. A proactive maintenance strategy helps extend equipment life while lowering energy and maintenance costs.

Below is a practical, step-by-step guide to effective chiller tube maintenance.

Step 1: Start With Thorough Tube Cleaning

Cleaning is the foundation of effective chiller tube maintenance. While a basic water flush can remove loose debris, it typically leaves behind scale and deposits—especially in tubes with ridges or enhanced surfaces.

Mechanical Tube Cleaning

Rotary tube cleaning systems equipped with brushes are highly effective at removing stubborn fouling. The rotating action allows brushes to reach grooves and irregular surfaces where buildup commonly occurs.

When selecting brushes, match the brush type to the fouling:

  • Soft fouling (algae, mud, biofilm) requires softer brushes

  • Hard fouling (scale, mineral deposits) requires more aggressive brush materials

Some cleaning systems also allow the application of corrosion inhibitors or antimicrobials during cleaning to help reduce future fouling.

Chemical Descaling (When Needed)

For severe buildup such as calcium, lime, or rust, chemical descalers may be required. Always confirm that cleaning chemicals are compatible with tube materials, especially for copper alloys or stainless steel. Consulting the equipment manufacturer or a specialist is recommended before chemical use.

Best practice: Perform tube cleaning at least annually, or biannually for high-use systems.

Step 2: Perform Eddy Current Testing

Eddy current testing is a non-destructive inspection method used to evaluate tube integrity over time. While it does not detect active leaks, it can identify early-stage problems such as:

  • Corrosion and erosion
  • Mechanical damage
  • Wall thinning
  • Manufacturing or installation defects

During testing, a probe generates a magnetic field inside the tube. Any disturbance in the signal indicates a potential defect at that location.

Recommended frequency:

  • Chillers: every 2–3 years
  • Evaporators: every 3–5 years

This testing helps facility teams plan repairs or replacements before failures occur.

Step 3: Optimize Water Quality and Treatment

Water quality directly impacts how often chiller tubes need to be cleaned. Poor water chemistry accelerates scaling, fouling, and corrosion.

Closed-Loop Systems

Most chillers operate in closed-loop systems, which generally require a one-time chemical treatment to inhibit corrosion and biological growth.

Open-Loop Systems

Condenser systems and cooling towers often operate as open-loop systems and typically require continuous water treatment to manage minerals, biofouling, and debris.

Water treatment programs should be tailored to local water conditions. A qualified water treatment specialist can analyze water chemistry and recommend appropriate solutions.

Step 4: Monitor Temperature and Flow Rate

In addition to water chemistry, operating conditions influence chiller performance:

Water temperature: Cooler water improves heat transfer efficiency, though lowering temperature should be considered a temporary efficiency boost, not a substitute for cleaning.

Flow rate: Optimal flow velocity typically ranges between 3 and 12 feet per second.

  • Low flow can cause laminar conditions and reduced efficiency
  • Excessive flow can lead to vibration, tube wear, and mechanical damage

Maintaining proper operating parameters helps prevent fouling and mechanical stress.

Step 5: Create a Preventive Maintenance Plan

Preventive maintenance is key to long-term chiller performance. A structured plan should include:

  • Routine inspections

  • Scheduled cleanings

  • Periodic testing

  • Water treatment monitoring

Maintaining a daily or weekly operating log allows facility managers to track performance trends such as pressure changes, temperature differentials, and energy use. These trends help determine optimal maintenance intervals and identify issues early—before they become costly repairs.

Over time, this data supports a customized maintenance schedule tailored to your specific system.

Step 6: Know When Replacement Makes Sense

Even with excellent maintenance, chillers have a finite lifespan. As systems approach 25–30 years of service, maintenance costs often rise while efficiency declines. Frequent tube failures, persistent performance issues, or outdated designs may indicate that replacement is the more economical option.

When evaluating a new chiller or heat exchanger, work with a manufacturer that offers engineering expertise, durable materials, and application-specific designs to ensure long-term performance. Our engineers are here to help identify shell and tube requirements for a wide range of assets, including chillers. Request a quote today.